● Full electrical parameters Measurement
● Bidirectional energy measurement
● Rated Voltage: AC230V
● Input Current: 80A, 120A, 200A, 300A
● RS485 interface and Modbus RTU protocol
● Application: PV grid-connected system, micro inverter system, energy storage system, AC coupling system etc.

General
ADL200 single phase din rail electric kWh energy meter is designed for single phase active energy measurement on low voltage system, in the same time it can measure the electrical parameters like voltage, current, power and so on. There is also RS485 communication can be chosen.
LCD display and electricity pulse output function is installed in the power meter; clock, rate period parameters can be set also. Data swap with the super ordination machine via RS485 communication interface greatly facilitate the power automated administration.
This power meter has advantages of smaller volume, high precision, good EMC, easily installing etc. All meters meet the related technical requirements of electronic power meter in the IEC62053-21、IEC62053-22 standards.
Dimension
Wiring
Wiring sample of current and voltage
Installation
35mm Din Rail Installation
Typical Connection
Photo on Site
Related Solution
Electric Energy Management System
Item |
Performance Parameters |
|
Model Series |
ADL200N-CT |
ADL400N-CT |
Grid |
Single-phase |
Three-phase four-wire, three-phase three-wire, single-phase three-wire
|
Rated voltage |
230V |
Single-phase: 240/480V |
Three-phase: 3×230/400V、3× 277/480V |
||
|
Overload |
1.2 times rating (continuous) 2 times the rating for 1 second |
Power consumption |
<0.2VA |
|
Accuracy class |
Error ±0.5% |
|
Input current |
80A, 120A, 200A, 300A |
80A, 120A, 200A, 300A, 3×80A, 3× 120A, 3×200A, 3×300A |
Overload |
1.2 times rating (continuous) 2 times the rating for 1 second |
|
Power consumption |
<0.2VA |
|
Accuracy class |
Error ±0.5% |
|
Power |
Active, reactive, apparent power, error ±0.5℅ |
|
Grid frequency |
45~65Hz, error ±0.5% |
|
Response rate |
≤100ms (voltage, current, power) |
|
≤1s (electrical energy) |
||
Electric energy |
Active energy: Class B (split current transformer) / Class C (closed Reactive energy (Class 2 accuracy) |
|
Electrostatic discharge immunity class III |
||
Electrical fast transient burst immunity class IV |
||
Surge (shock) immunity Class IV |
||
Power frequency withstand voltage |
Between communication and signal input, AC4kV 1min |
|
Insulation resistance |
Input and output terminals to casing >100MΩ |
|
Interface and communication |
RS485 interface and Modbus RTU protocol |
|
Communication address range |
Modbus RTU: 1~ 247; |
|
Baud rate |
Support 1200bps ~ 38400bps |
|
Operating temperature |
-40℃~+70℃ |
|
Storage temperature |
-40℃~+70℃ |
|
Relative humidity |
≤95℅ (without condensation) |
|
Altitude |
≤3000m |