● Usually installed in the busbar start box and plug-in box
● Measurement: AC/DC busbar voltage, current, harmonics and other parameters.
● Temparature, Leakage Monitoring, 4DI2DO
● 48VDC, 240VDC, 336VDC or 3×220/380VAC
● U, I, P, Q, S, PF, kWh, kvarh
● DIN 35mm Installation
● RS485/Modbus-RTU or LORA Communication
General
AMB Smart AC bus bar monitoring is a new development to cater for smart power bus bar. It consists of a feeding detection module and a tapping detection module and integrates functions of conventional power measurements, electricity monitoring, consumption assessment and control. It also boasts the online alarm function and enables the independent off-line operation. It monitors the bus bar interface temperature in real time.
It is necessary to real-time monitor energy consumption and power quality of end load in smart track busway. Data can be uploaded to monitoring system by local touch screen through RS485 and it can realize real-time monitoring of the whole power distribution system.At the same time,it can monitor real-time temperature at the busway connector and plug-in box interface to ensure safe and reliable operation of the busway.
Wiring
Dimension
Monitoring System
Typical Connection
Application
Photos on Site
Related Solution
Smart Busway Monitoring Solution
Voltage |
Rated Value |
3x220/380VAC |
Range |
±20% |
|
Overloading |
1.2 times than the rated voltage value continuously or 2 times than the rated voltage value instantaneously per second |
|
Current |
CT |
AMB100-A: 5A/2.5mA, 100A/20mA, 400A/100mA, 600A/100mA; AMB110-A: 100A/20mA |
Range |
1%-120% |
|
Overloading |