General
AMC16Z series AC precision power distribution monitoring device is specially designed for data center server power management.The device designed exquisite, can provide A + B 2 incoming and 96 outgoing’s electrical parameters, the input and output switch and the state of lightning protection device with real-time monitoring. All alarm threshold of measurement channels can be set in separate. Over-outgoing triggers system acoustooptic warning immediately. Highly integrated monitoring loop is realized in the volume of traditional instruments.
Monitor the full power parameters of A+B double-way three-phase AC incoming circuit, 6-way switch state monitoring, 2-way alarm output, 2-way leakage monitoring, 1-way temperature and humidity detection, 1-way RS485 communication, and phase-sequence detection.
Dimension
Wiring
Application
Typical Connection
Photo on Site
Related Solution
Precision Distribution Monitoring For IDC
Technical parameter | AMC16Z-ZA | |
Measured parameters | Vbltage, current, frequency, active power, reactive power, power factor, active power, reaclive power | |
Zero ground voltage, neutral line current, total harmonic content (THD), 2-63 harmonics, current and voltage unbalance degree, current K coefficient (KF), voltage crest coefficient (CF), telephone waveform factor (THFF), peak voltage, voltage and current sequence quantity, environmental temperature and humidity. | ||
Busbar voltage | Rated | 220VAC |
Measurement | ±20% | |
Overload | Instant voltage 2times/second | |
C urrent incoming circuit | Rated | Twice 5A |
Range | 0〜6A | |
Overload | Duration 1.2 times, instantaneous 10 timcs/second |