AID10 Remote Alarm Indicator
● Remote monitoring
● LED indicators: On, Insulation, Overload, Overtemp
● Mute button
● Test button
● Auxiliary power supply: DC24V
● RS485(MODBUS-RTU)
  • product detail
  • PARAMETER
  • ISOLATION POWER CABINET

General

AID series alarm and display device is a remote display and sound and light alarm device by using advanced fieldbus communications technology. The device can be installed on the operating room or ICU, the medical staff can easily know the status of medical isolated power systems, and the type of fault when the system fails.


Function

- The insulation resistance alarm value, load current alarm value and transformer temperature alarm value of the system can be set remotely.

- When the system appears insulation fault, overload, transformer temperature over limit and wiring fault, alarm and display instrument gives out the corresponding sound and light alarm, and has the function of eliminating sound alarm.

- Using advanced fieldbus technology, the remote monitoring function can be realized by real-time data interaction with the insulation monitor.

- It can monitor one set of AIM-M100 insulation monitor and be used for installation by embedding into wall.

- It can be applied to monitor operating room or ICU only using single set of isolated power.

Wiring & Installation


Dimension

  • Front view
  • Side view


Product Selection



Structure



LED Indicator Instructions

Indicator light

Instructions

On

When the instrument operation is normal, the indicator flashes, with the flashing frequency of about one time per second.

Insulation

When the insulation resistance exceeds the alarm value, the indicator flashes to alarm.

Overload

When the load current exceeds the rated current of the transformer, the indicator flashes to alarm.

Overtemp

When transformer temperature exceeds alarm value, indicator flashes to alarm.


Button Function Description

Button
Function Description
Mute
When there is alarm, press this button to eliminate the alarm sound.
Test
Used to start the self-test function of monitor.

Common Problem

For common problems, the causes can be determined and the faults can be eliminated according to the phenomenon of each instrument and the fault types:

Fault phenomenon

Possible Causes and Troubleshooting

Abnormal communication

1) The address of AIM-M10 is not set to default 1, or BUAD is not set to default 9600, so it should be set to default value.

2) The communication line with AIM-M10 is not well connected. Check the communication line and confirm that the matching resistance is well connected.

Parameter               Type

AID10

AID150

Auxiliary power supply

Voltage

DC 24V

Consumption

< 0.6W

Insulation alarming range

——

14A, 18A, 22A, 28A, 35A, 45A

Temperature alarm setting range

——

0~+200

Number of monitored systems

1

16

Alarm method

Sound-light alarm

Alarm type

Insulation failure, overload, overheat, equipment failure

Communication mode

RS485, MODBUS-RTU

Display mode

LED display

128×64  LCD display



Feedback form contact with us
Related Product
Ground Fault Detection And Location Relay
Ground Fault Detection And Location Relay
Quality Ground Fault Detection And Location Relay manufacturers & exporter - buy Ground Fault De...
Learn More
ASG150 Test Signal Generator
ASG150 Test Signal Generator
You can buy good quality ASG150 Test Signal Generator, we are the best distributor from China market...
Learn More
ACLP10-24 DC Power Supply
ACLP10-24 DC Power Supply
Acrel is the best ACLP10-24 DC Power Supply manufacturer in China. Offering quality product to globa...
Learn More
Product Catalog