General
AMC series AC multi-function panel meter is a smart meter designed for power monitoring needs of power systems, industrial and mining enterprises, utilities, and intelligent buildings, etc. It integrates measurement of power parameters, such as single-phase or three-phase current, voltage, active power, reactive power, apparent power, frequency, power factor.
High-brightness LED/LCD display interface, parameter setting and control through buttons, ideal for real-time power monitoring systems. Can directly replace conventional power transmitters and measuring instruments. As an intelligent, digital front-end acquisition component, the instrument has been widely used in various control systems, SCADA systems and energy management systems.
Accuracy Active energy: Class 0.5
Frequency Range: 45-65Hz
Auxiliary power supply: AC/DC 85~265V
Pulse output: 1600-160000imp/kWh
Auxiliary power supply: power consumption≤10VA
Installation: Panel mounted
Panel size (L×W): 96*96mm
Cut out (L×W): 92*92mm
Housing size (L×W): 90*90*77.8mm
Relay: DC 30V/3A AC 220V/3A
Consumption: 0.2%
Specification
Meter type
|
Basic function
|
Optional function
|
|
AMC72-E4/KC
AMC72L-E4/KC
|
Three phase voltage, Zero sequence voltage
Three phase current, Zero sequence current
Three phase active power, Total active power
Three phase reactive power, Total reactive power
Three phase apparent power, Total apparent power
Three phase Power factor, Total power factor
Frequency, Voltage phase angle, Voltage and current imbalance, Forward and reverse power
Four quadrant energy metering, System time display
1 channel RS485 interface / Modbus-RTU protocol and the statute DLT645.
|
①2DI+2DO+1Ep(K)
②4DI+2DO(K)
③Event record (SOE)
④2-31st and total harmonics measurement (H)
⑤2DI+2DO+1M(KM)
|
|
AMC96-E3/KC
AMC96L-E3/KC
|
①4DI+2DO+1Ep(K)
②2DI+2DO+1Ep(K)
③Event record (SOE)
④2-31st harmonic measurement (H)
⑤2-channel analog output (M)
|
||
AMC96-E4/KC
AMC96L-E4/KC
|
|||
AMC72-E/KC
AMC72L-E/KC
|
single-phase voltage,single-phase current
active power, reactive power, apparent power
Power factor, Frequency, Four quadrant energy metering, System time display
1 channel RS485 interface / Modbus-RTU protocol and the statute DLT645.
|
①2DI+2DO+1Ep(K)
②4DI+2DO(K)
③Event record (SOE)
④Total harmonic measurement (H)
⑤2DI+2DO+1M(KM)
|
Dimension
AMC96 Appearance Size
AMC96 Installation Dimension
LCD Display
Wiring
Typical Connection
Related Solution
Electric Energy Management System
Technical parameters
|
Value
|
|||
Input
|
Connection
|
3-phase-3-wire, 3-phase-4-wire
|
||
Frequency
|
45-65Hz
|
|||
Voltage
|
Rating:
single-phase: AC 100V、400V
Three-phase: AC 3×57.7V/100V(100V)、3×220V/380V(400V)、3×380V/660V(660V) (96 size only)
Note: 72 profile not suitable for high voltage applications
|
|||
Overload: 1.2 fold rating (continuous): 2 fold rating for 1 second
|
||||
Power consumption: < 0.5VA
|
||||
Current
|
Rating: AC IA、5A
|
|||
Overload: 1.2 fold rating(continuous); 10 fold rating for 1 second
|
||||
Power consumption: < 0.5VA
|
||||
Output
|
Electric energy
|
Output mode: open-collector photo-coupler pulse
|
||
Pulse constant: 10000imp/kWh(settable), see wiring diagram for details;
|
||||
Communication
|
RS485port, Modbus -RTU protocol, DLT645 protocol(versions 07 and 97), baud rate 1200 ~ 38400
|
|||
Function
|
Switching input
|
Dry contact input, built-in power supply;
|
||
Switching output
|
Output mode: Relay normally open contact output
|
|||
Contact capacity: AC 250V/3A、 DC 30V/3A
|
||||
Analog output
|
1-5V, 4 - 20mA
|
|||
Accuracy class
|
Frequency: 0.05Hz, Current、Voltage: Class 0.2, Reactive power: Class 1, Reactive Electric energy: Class 1, active power: Class 0.5, active electric energy: Class 0.5, 2-31st harmonic measurement: ±1%
|
|||
Power supply
|
AC/DC 85-265V or DC24V(±20%) or DC48V(±20%)
power consumption≤10VA
|
|||
Security
|
Power frequency withstand voltage
|
Between Power supply//Switching Output// Current Input//voltage Input and Transmitting// Communication //Pulse Output//switching
input AC 2 kV 1min;
Between Power supply、switching output、Current Input、voltage Input AC 2 kV 1min;
Between Transmitting、Communication、Pulse Output、switching input AC 1kV 1 min;
|
||
Insulation resistance
|
Input、Output end to machine enclosure >100MΩ
|
|||
Environment
|
Temperature
|
Work: -25°C~+65°C; Storage: -40°C ~+80°C
|
||
Humidity
|
≤93%RH Non-condensing
|
|||
Altitude
|
≤2500m
|